Experience & projects

Case study

CCS Network (ME) Ltd
CCS Network (ME) Ltd

Dungeness — metalwork trial

Site:
Dungeness 400 kV substation
Customer:
National Grid
Date of application:
September 2020
Pollution type:
Water and saline air on painted metalwork
Equipment:
A section of roller shutter and a section of gutter
After
After

The challenge

Salt air at Dungeness affects steelwork as well as insulation. On a section of roller shutter on the north side, and a section of gutter on the south side facing the sea, the anti-corrosion paint was estimated at more than 10 years old. Ultraviolet light had weakened the paint and it had cracked, so moisture had reached the steel.

The solution

Loose rust and paint were removed by scraping and wire brushing, and the surfaces were wiped with solvent. An RTV silicone anti-corrosion coating was applied by air-assisted spray to a section of the shutter and a section of the gutter. The trial was carried out on 15 September 2020.

The result

The trial application was completed on the shutter and the gutter. CCS planned to inspect the test areas after one year.

Before
Before

Long-term performance

Survey date:
28 September 2021
Customer:
National Grid
Pollution type:
Saline
Equipment:
400 kV insulators, including SGT1

On 28 September 2021 CCS surveyed the 400 kV insulators. Dungeness is an exposed coastal substation, and salt on the porcelain is a flashover risk. The insulators are coated with RTV silicone HVIC. On SGT1 the same day, hydrophobicity was typically HC1 to HC2, and it was better on the south and east faces than on the north and west. CCS recommended an overcoat of RTV silicone HVIC. The photograph shows those coated posts in service.

In service
In service

Download PDF

CCS Network (ME) Ltd. www.ccs-network.com