Grain 400 kV — replacing water washing with RTV silicone HVIC

Site:
Grain 400 kV substation
Customer:
National Grid
Survey date:
25 June 2021
Pollution type:
Saline
Equipment:
400 kV insulators
Current protection:
Automated water wash
In service
In service

The challenge

The 400 kV insulators at Grain were kept clean by an automated water-wash system, operated to a regular schedule. Washing is not a coating. The system requires a major overhaul, and maintenance of the wash plant itself is costly. In the recent past the substation flashed over while the wash was running. That flashover tripped the circuit and damaged apparatus.

The solution

On 25 June 2021 CCS surveyed the 400 kV yard for National Grid. This was a condition assessment, not an application. Some circuits at Grain are already coated with RTV silicone HVIC, and that coating has provided reliable, maintenance-free protection. The recommendation was to take the water wash out of service and to apply RTV silicone HVIC to the insulators that still depend on washing.

The result

A hydrophobic coating removes the need to keep a wash system in service, and it remains on the porcelain between the intervals at which a wash would have run. The survey recommendation to National Grid was to deactivate the wash and to protect the porcelain with RTV silicone HVIC. The photographs show the yard in service.