Margam — Baglan Bay L13 isolator posts
Margam substation, Baglan Bay L13, South Wales
National Grid
June 2020
Industrial pollution
6 isolator posts, 275 kV

The challenge
The six 275 kV isolator posts had been protected with hydrocarbon grease for an estimated 15 years or more, against industrial pollution. The grease had become saturated with surface contaminants and was no longer effective. Removal becomes more difficult when that maintenance has not been kept up.
A polluted porcelain surface becomes hydrophilic. Wetting can lead to leakage current, arcing and tracking, and ultimately to flashover.
The solution
On 23 June 2020 the grease was removed and the porcelain was cleaned back to the glaze. RTV silicone HVIC was sprayed to between 360 and 500 microns. Temperature, humidity and batch numbers were recorded. Adhesion, thickness and hydrophobicity were checked.
The result
Adhesion, thickness and hydrophobicity were checked and found satisfactory. The six isolator posts were returned to service with a hydrophobic coating in place of the saturated grease. The coating is designed to remain in service without a further cycle of greasing.