How the work is done
Supply and application
CCS Network (ME) Ltd supplies and applies CSL Silicones Si-COAT 570 for network operators, generators and their contractors. Product can be supplied on its own, or supplied and applied by CCS. Insulator work and metalwork can be planned in the same outage, with one product and one crew, to save time and application cost. Reactor-coil overcoating is offered as a dedicated service, often during a planned outage.
- 1
Product supply and distribution
Supply only, or supply and apply. UK stock is held for prompt dispatch and is available for delivery or for EXW (Ex Works) collection, where the buyer collects from CCS in the United Kingdom. Larger or international orders are shipped direct from the manufacturer, CSL Silicones. Lead times are quoted with each order. The technical data sheet and the safety data sheet are supplied with the product. Application guidance and training for a customer’s own team are available.
- 2
New coating
Surface cleaning and preparation, application of Si-COAT 570 to the specified dry film thickness, and a written quality record.
- 3
Overcoating
Inspection of existing RTV silicone HVIC, cleaning in accordance with IEEE 957, verification of adhesion and cleanliness, then a new layer of about 10–12 mils (250–320 µm). Total thickness of old plus new coating should not exceed 800 µm.
- 4
Inspection and hydrophobicity assessment
Visual condition, hydrophobicity class, remaining thickness, and a written recommendation — overcoat, local repair, or leave in service.
- 5
Metalwork in the same outage
Corrosion control on gantries, structures and cabinets using the same Si-COAT 570 product, programmed with the insulator work.
- 6
Reactor-coil overcoating
Inspection of factory-applied or in-service RTV silicone HVIC, patch repair of local damage, or full overcoat, or strip and re-coat, in accordance with the CCS reactors method statement.






Application methods: airless air assisted spray (recommended) or brush and roller.
CCS typically plans a maintenance overcoat of insulator and reactor coatings at about ten years, subject to inspection.