Application 1
Flashover prevention on insulators and bushings
Pollution on high-voltage insulators can allow leakage current to develop and, in wet conditions, can lead to flashover. Si-COAT 570 is applied as a high-voltage insulator coating on insulators and bushings so that the surface remains hydrophobic, leakage current is suppressed, and the risk of pollution-related flashover is reduced.
The coating can be used, unprimed, on glass, porcelain and polymer (silicone and EPDM) insulators, on both new and in-service equipment, and as a refresh coat over an existing RTV silicone HVIC that is still well adhered. It is designed for substations and lines, on AC and DC systems, from distribution voltages to very high transmission voltages.





- Practical application guidance on the data sheet: 380 µm ± 100 µm dry film thickness, in accordance with IEEE Std 1523-2002.
- The entire insulator should be coated to a minimum of 15.0–20.0 mil (381–508 µm) DFT; the maximum advisable DFT is 50 mil (1,270 µm).
- CCS field practice is typically to work to about 500 µm (0.50 mm) on new insulator coating, which sits in the upper part of that band and is consistent with earlier RTV silicone HVIC practice of 0.5 mm ± 0.14 mm.